Products > GEO POLAR Series > Specs

Performance Specifications at 50F. (EWT) Entering Water Temperature.

Based on ARI Standard 325 Rating Conditions, (Open Loop).

Unit Size

Nominal CFM

GPM

Cooling BTU/hr

EER at 50F. ewt

Heating
BTU/hr

COP at
50F. ewt

V-24D

1000

3.5

26,000

14.1

24,000

3.4

V-30D

1200

4

32,000

14.2

30,000

3.4

V-36D

1400

5

42,000

14.2

36,000

3.4

             

V-42D

1600

6

45,000

14.1

42,000

3.2

V-48D

1800

6.5

50,000

14.1

48,000

3.4

             

V-54D

2000

7

54,000

13.8

56,000

3.4

V-60D

2200

8

62,000

13.7

62,000

3.4

V-66D

2200

8.5

66,000

13.6

66,000

3.3


Performance Specifications at 32F. (EWT) for Heating and 77F. EWT for Cooling.

Based on ARI Standard 330 Rating Conditions, (Closed Loop).

Unit Size

Nominal CFM

GPM

Cooling BTU/hr

EER 77F. ewt

Heating BTU/hr

COP 32F. ewt

V-24D

1000

6

22,000

13.3

20,000

3.1

V-30D

1200

8

28,000

13.4

25,000

3.0

V-36D

1400

9

36,000

13.4

30,000

3.1

             

V-42D

1600

10

40,000

13.1

36,000

3.0

V-48D

1800

12

44,000

13.4

41,000

3.1

             

V-54D

2000

14

48,000

13.2

48,000

3.1

V-60D

2200

16

54,000

13.2

54,000

3.1

V-66D

2200

16

58,000

13.1

58,000

3.0